Inches of Water (inH2O) to PSI Converter

Select the water reference temperature most calculators silently fix — and read your DP transmitter range straight across into psi, mbar and kPa.

Formula: psi = inH2O × factor(T). Reciprocal of our psi to inches of water converter.

What an inch of water actually measures

An inch of water column is the pressure produced by a one-inch-tall column of water: inH2O = ρwater × g × h, with h = 0.0254 m and g = 9.80665 m/s². Because water is light compared with mercury, the unit resolves very small pressures finely — one psi is about 27.7 inH2O, so a span that would be a fraction of a psi becomes tens of readable inches. That is exactly why duct static pressure, filter and coil differential, burner draft and low-density liquid level are graduated in inH2O (also written inWC, in. w.c. or iwg) rather than psi. Converting to psi is what you do when a gauge, a transmitter output or a spec sheet speaks psi and the rest of the system speaks water column.

The reference temperature most converters hide

Water density falls as it warms, so the inH2O-to-psi factor depends on the water temperature the unit is referenced to — and most online converters fix one value without telling you which. The three references actually used in industry differ by about 0.18%:

Reference temperature Water density (kg/m³) 1 inH2O = 1 inH2O =
39.2°F / 4°C (ISO) 999.972 0.0361263 psi 2.4908 mbar
60°F / 15.56°C (US default) 999.017 0.0360918 psi 2.4884 mbar
68°F / 20°C (lab) 998.207 0.0360625 psi 2.4864 mbar

The selector above defaults to 60°F, the convention behind most North American DP and HVAC instrument scales. On a precision transmitter specified to ±0.1% FS, the 4°C-versus-60°F gap is roughly the same size as the accuracy budget, so it is worth matching the reference your instrument’s datasheet or governing standard uses rather than accepting whatever a hidden factor assumes.

inH2O to psi: worked examples

Worked at the 60°F reference. To convert, multiply the inches of water by the factor for your reference temperature; psi = inH2O × 0.0360918.

Inches of water psi mbar kPa
10 inH2O 0.3609 psi 24.884 mbar 2.4884 kPa
30 inH2O 1.0828 psi 74.653 mbar 7.4653 kPa
100 inH2O 3.6092 psi 248.844 mbar 24.8844 kPa
250 inH2O 9.0229 psi 622.110 mbar 62.2110 kPa
400 inH2O 14.4367 psi 995.376 mbar 99.5376 kPa

A single inch is the anchor worth memorising: 1 inH2O = 0.0360918 psi = 2.4884 mbar = 0.24884 kPa at 60°F. At the ISO 4°C reference the same inch is 0.0361263 psi — close, but not identical, which is the whole point of stating the reference.

DP transmitter range cheat-sheet

Low-range differential transmitters are usually catalogued in inH2O. This table converts the common spans to psi, mbar and kPa at 60°F so you can match a water-column requirement to a transmitter range without re-deriving the factor each time.

inH2O range psi mbar kPa
0–10 inH2O 0–0.361 psi 0–24.88 mbar 0–2.488 kPa
0–25 inH2O 0–0.902 psi 0–62.21 mbar 0–6.221 kPa
0–100 inH2O 0–3.609 psi 0–248.84 mbar 0–24.884 kPa
0–250 inH2O 0–9.023 psi 0–622.11 mbar 0–62.211 kPa
0–400 inH2O 0–14.437 psi 0–995.38 mbar 0–99.538 kPa

The HMK HM30 covers the bottom of this band for air and gas duct work, while the HM31 carries the higher spans and liquid service; both are graduated so the inH2O figure on the drawing maps directly onto the ordered range.

Notation traps: inH2O vs inWC vs iwg vs iwd

The same physical unit travels under several labels, and mixing them up is a common source of confusion on drawings:

Symbol Reads as Where it appears
inH2O / inWC / in. w.c. inches of water column generic; the unit itself
iwg / in. w.g. inches of water, gauge HVAC static pressure, referenced to atmosphere
iwd inches of water, differential filter / coil ΔP across two taps

The arithmetic is identical — an inch is an inch — but the reference is not: a gauge (iwg) reading is against atmosphere, while a differential (iwd) reading is the drop across two ports. Always confirm whether a stated inH2O figure is gauge or differential before you size a transmitter to it, because the same number on the wrong reference points at the wrong instrument.

Where inH2O shows up in the field

Typical bands help sanity-check a converted figure. Duct static pressure in commercial HVAC sits roughly between 0.5 and 6 inH2O; a loaded filter or coil differential is often alarmed at 1–3 inH2O; combustion air and furnace draft run from a fraction of an inch to a few inches; clean-room and containment differentials are tiny, around 0.01–0.05 inH2O; and low-density liquid level in shallow tanks can read tens of inches of water. If a converted psi value lands far outside the band you expect, the cause is usually a wrong reference temperature, a gauge-versus-differential mix-up, or a transmitter range that does not match the service.

Frequently Asked Questions

Is 1 psi 27.68 or 27.7 inches of water?

Both, depending on the water reference temperature. At 4°C (ISO) 1 psi is 27.6807 inH2O; at 60°F (the common US instrument reference) it is 27.7071 inH2O; at 68°F it is 27.7296 inH2O. The converter lets you pick the reference rather than hiding it.

What is the difference between inH2O at 4°C and 60°F?

Water is denser at 4°C, so an inch of it makes slightly more pressure: 1 inH2O = 0.0361263 psi at 4°C versus 0.0360918 psi at 60°F. The gap is about 0.18%, which matters when you calibrate a high-accuracy DP transmitter.

How many inH2O is a typical DP transmitter range?

Low-range DP transmitters are commonly built for 0–10, 0–25, 0–100, 0–250 or 0–400 inH2O. At 60°F those correspond to about 0.36, 0.90, 3.61, 9.02 and 14.4 psi respectively.

Need the transmitter behind the number?

Tell us the range in inH2O or psi and the service — air, gas or liquid DP — and we will spec the right differential-pressure transmitter.

Request a QuoteBrowse DP Transmitters

LJ

Lin Jun · Pressure Instrumentation Engineer

Specialises in pressure and differential-pressure measurement — sensor selection, range matching and field calibration across HVAC, process and OEM applications. He built this converter from the low-DP and air-pressure unit work that comes up on real commissioning and calibration jobs, where the reference temperature behind a water-column factor is rarely stated but quietly moves the result.

Read more from Lin Jun →